Description
Management of the output state if the interval time of RS485-bus communication failure is greater than a configurable time (up to 25 sec).
The module Z-D-OUT controls 5 relays digital output (OUT1-OUT5).
Z-D-OUT is 5 SPST relay output module with common line, capacity 5 A – 250 Vac resistive, 2 A inductive. The module has removable terminals with section of 2.5 mm2. Z-D-OUT offers possibility of setting relay safety status at start-up or without communication.
Also the module allows safety time setting from 0,5 to 2,5 s. RS485 serial communication supports Modbus-Rtu protocol, maximum 32 nodes. Max 3-way isolation module is 1.500Vac.
Management of the output state if the interval time of RS485-bus communication failure is greater than a configurable time (up to 25 sec).
The module Z-D-OUT controls 5 relays digital output (OUT1-OUT5).
Datasheet |
|